Mounting the Duct Averaging Sensor - Johnson Controls - Part No. 24-4034-107 - TE-6300P - TE-63xxP - Temperature Sensor - TE-6300P Series Temperature Sensors

TE-6300P Series Temperature Sensors Installation Guide

Brand
Johnson Controls
Product name
TE-6300P Series Temperature Sensors
Document type
Installation Guide
Document number
Part No. 24-4034-107
Document revision
R
Revision date
2021-02-26
Language
English

About this task

See Figure 1 to mount a single duct averaging sensor.

See Figure 2 to mount four duct averaging sensors in series-parallel for larger ducts.

Figure 1. Installing the Duct Averaging Sensor
Figure 2. Series-parallel mounting configuration

Mount the duct averaging sensor as follows:

Procedure

  1. Drill a 1-3/8 in. (35 mm) diameter hole at the desired mounting location.
  2. Use the mounting plate as a template to drill four 1/8 in. (3 mm) holes for the screws.
  3. Mount the averaging sensor probe inside the duct using a TE-6001-8 or equivalent 3 in. (76 mm) minimum radius temperature element holder.
    Important: Do not bend the sensor probe tighter than a 3 in. (76 mm) radius, a 6 in. (152 mm) diameter, to avoid permanently damaging the sensor.
    Note: Platinum sensor models include two TE-6001-8 Element Holders.
  4. Insert the sensor probe into the sensor holder and mounting plate assembly. Firmly tighten the sensor holder set screw.
  5. Follow Steps 3 through 7 in Mounting the Duct Sensor.