Configuring the T612DFH-4 and T612DFH-4+PIR Thermostat Controllers - Johnson Controls - 24-9890-1397 - T612DFH-4 - T612DFH-4+PIR - T612DFH-4 and T612DFH-4+PIR Thermostat Controllers with Fan Control and Occupancy Sensing Capability

T612DFH-4 and T612DFH-4+PIR Thermostat Controllers with Fan Control and Occupancy Sensing Capability Installation Guide

Brand
Johnson Controls
Product name
T612DFH-4 and T612DFH-4+PIR Thermostat Controllers with Fan Control and Occupancy Sensing Capability
Document type
Installation Guide
Document number
24-9890-1397
Document revision
B
Revision date
2021-01-07
Product status
Discontinued
Language
English

About this task

The T612 Thermostat Controller comes from the factory with default settings for all configurable parameters. The default settings are shown in Table 1. To reconfigure the parameters via the thermostat controller, follow the steps in this section.

Procedure

  1. To access the Installer Configuration Menu, press and hold the center key for approximately 8 seconds.
    Note: If the Password parameter is configured, Password 0 appears on the thermostat controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the MODE key to proceed through the Installer Configuration Menu parameters.
  2. Once the Installer Configuration Menu begins, press and release the center key to scroll through the parameters listed in Table 1.
  3. When the desired parameter is displayed, use the UP/DOWN arrow keys to choose the desired selection option.
  4. Press and release the center key to continue scrolling through the parameters.
    Note: Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed in Table 1.

Results

When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat controller reverts to the Status Display Menu.