Supply air temperature control - Johnson Controls - LIT-12011950 - Building automation software - Smart Equipment Controller - 5.0

Smart Equipment Controls Sequence of Operation Technical Bulletin

Product
Building Automation Systems > Building Automation Systems > Smart Equipment Controller
Document number
LIT-12011950
Version
5.0
Revision date
2024-06-06
Product status
Active

Setpoints and related data

The setpoints and related data include the following items:

  • Operational VAV cooling setpoint (OprVAVClg-Sp)
  • VAV cooling supply air temperature upper setpoint (SATUp-Sp)
  • VAV cooling supply air temperature lower setpoint (SATLo-Sp)
  • VAV supply air temperature reset setpoint (SATRst-Sp)
  • Operational space temperature (OprST)
  • Temperature/humidity control enable (TempHumCrl-En)
  • Temperature/humidity setpoint (TempHum-Sp)