The timers include the following items:
- Anti-short cycle delay (ASCD) cool: 300 seconds
- Min comp runtime: 180 seconds
- Min heat runtime: 180 seconds
- ASCD heat: 120 seconds
- Heat to cool delay: 300 seconds
- Cool to heat delay: 120 seconds
The sequences described within this document assume all safeties are closed.
A heating to cooling and cooling to heating changeover timer must expire before any heating or cooling functions occur.