Timers - Johnson Controls - LIT-12011950 - Building automation software - Smart Equipment Controller - 5.0

Smart Equipment Controls Sequence of Operation Technical Bulletin

Brand
Johnson Controls
Product name
Smart Equipment Controller
Document type
Technical Bulletin
Document number
LIT-12011950
Version
5.0
Revision date
2024-06-06
Product status
Active
Language
English

The timers include the following items:

  • Anti-short cycle delay (ASCD) cool: 300 seconds
  • Min comp runtime: 180 seconds
  • Min heat runtime: 180 seconds
  • ASCD heat: 120 seconds
  • Heat to cool delay: 300 seconds
  • Cool to heat delay: 120 seconds

The sequences described within this document assume all safeties are closed.

A heating to cooling and cooling to heating changeover timer must expire before any heating or cooling functions occur.