Heat limit switches do not have to disable cooling (new in version 4.0) - Johnson Controls - LIT-12011950 - Building automation software - Smart Equipment Controller - 5.0

Smart Equipment Controls Sequence of Operation Technical Bulletin

Product
Building Automation Systems > Building Automation Systems > Smart Equipment Controller
Document number
LIT-12011950
Version
5.0
Revision date
2024-06-06
Product status
Active

On all previous software, the Heat Limit Switch would lockout both heating and cooling operation. An option to allow cooling operation while the Heat Limit Switch is in Alarm would allow the unit to cool as needed without risk to heat fault behaviors.

A user configuration option has been added which allows cooling functionality to ignore the Heat Limit Switch.

Enable Point Cooling Allowed During Heat Limit (CoolDuringHeatLimit).
  • Commissioning → Options
  • Details → Heating → Setup