While the functionality to detect if a damper feedback was out of calibration has always been in place, there existed no place for the end user to enable this functionality.

A point has been added to the Details → Economizer → Setup menu which allows this functionality to be enabled. The name of this point is “Calibration Fault Detect Enable” (CalFaultDetectEn).