Low ambient minimum position - Johnson Controls - LIT-12011950 - Building automation software - Smart Equipment Controller - 5.0

Smart Equipment Controls Sequence of Operation Technical Bulletin

Product name
Smart Equipment Controller
Document type
Technical Bulletin
Document number
LIT-12011950
Version
5.0
Revision date
2024-06-06
Product status
Active

Setpoints and related data

The setpoints and related data include the following items:

  • Low ambient economizer minimum position (LowAmb-MinPos)
  • Low ambient economizer setpoint (LowAmb-Sp)

Operation

The low ambient economizer minimum position overrides all other minimum position functions.

When the control is in the occupied mode, the FAN output is energized, and the operational OAT is below the low ambient economizer setpoint, the economizer is positioned to the low ambient economizer minimum position. When the Operational OAT is equal to or above the low ambient economizer setpoint, it exits the low ambient economizer setpoint mode.