4-pipe split sequence - Johnson Controls - LIT-12011950 - Building automation software - Smart Equipment Controller - 5.0

Smart Equipment Controls Sequence of Operation Technical Bulletin

Product
Building Automation Systems > Building Automation Systems > Smart Equipment Controller
Document type
Technical Bulletin
Document number
LIT-12011950
Version
5.0
Revision date
2024-06-06
Product status
Active

Inputs

The inputs include the following items:

  • Thermostat only (Tstat-Only) is set to yes
  • 4-pipe split enable (4pipeEna) is set to yes
  • Number of cooling stages (#ClgStgs)
  • Number of refrigeration systems installed (#RefrigSys)
  • Y1, Y2, Y3, Y4

Outputs

The outputs include the following items:

  • C1, C2, C3, C4
  • CN-FAN, CF2