Performance Data - Johnson Controls - LIT-1900857 - Backdraft Damper - RP-2000 Pressure Relief Backdraft Damper

RP-2000 Pressure Relief Backdraft Damper Catalog Page

Product
Dampers > Backdraft Dampers > RP-2000 Pressure Relief Backdraft Damper
Document number
LIT-1900857
Revision date
2021-03-10
Table 1. Performance Data
Pressure Drop (inches WG) - Fully Open 500 fpm 1,000 fpm 1,500 fpm 2,000 fpm
6 inch

24 inch

0.4

0.07

0.41

0.16

0.55

0.30

0.91

0.55

Maximum System Velocity 2,000 fpm
Leakage for 6” Diameter Damper
Static Pressure, inch WG 1.0 1.5 2.0 2.5 3.0
Leakage, cfm/sq ft 8.7 11.0 10.6 11.6 13.0
Temperature Rating -40 to 200°F (-40 to 93°C)
Approximate Weight 5 lb/sq. ft (2.27 kg/sq. ft)
Note: Dampers are tested at an AMCA Certified Laboratory using instrumentation and procedures in accordance with AMCA Standard No. 500, Test Methods for Louvers, Dampers, Shutters. All dampers are labeled as to direction of airflow and position during testing.