Submittal Specifications - Johnson Controls - LIT-1900246 - Round Balancing Damper - RB-2000 Round Balancing Damper

RB-2000 Round Balancing Damper Catalog Page

Brand
Johnson Controls
Product name
RB-2000 Round Balancing Damper
Document type
Catalog Page
Document number
LIT-1900246
Revision date
2021-03-10
Language
English

Furnish and install round balancing dampers manufactured by Johnson Controls.

  • Damper shrouds are to be constructed of formed 20-gauge G90 galvanized sheet steel or 304 stainless steel, mechanically joined.
  • Damper blades are to be constructed with single-piece galvanized steel or 304 stainless steel based on shroud material.
  • Damper performance shall not require tight shutoff. The damper must be rated to operate over a temperature range of -20°F to 200°F (-29°C to 93°C) or 20°F to 350°F (-29°C to 177°C), to be determined by the material.
  • Damper sizing shall be by the designer in accordance with accepted industry practices to insure proper system performance.