General information - Johnson Controls - LIT-12014365 - RA-1270 - Airflow Measuring Station - RA-1270 Fan Inlet Airflow and Temperature Measurement Station

RA-1270 Protocol Implementation Conformance Statement

Product
Controls > Temperature Controls > RA-1270 Fan Inlet Airflow and Temperature Measurement Station
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12014365
Revision date
06/02/2024
Product status
Active
Table 1. Protocol implementation conformance statement (PICS)
Specification Description
Date 02 October 2023
Vendor ID 692
Product name RA-1270 Electronic Fan Inlet Monitor
Product model number RA-1270
Firmware revision 2.0.0b01
Application software version: 1.1.1
BACnet protocol revision 14
Product description Electronic fan inlet monitor system
BACnet standard device profile BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks supported

Data Sharing - ReadProperty-B (DS-RP-B)

Data Sharing - WriteProperty-B (DS-WP-B)

Device Management - DynamicDeviceBinding-A (DM-DDB-A)

Device Management - DynamicDeviceBinding-B (DM-DDB-B)

Device Management -DynamicObjectBinding-B (DM-DOB-B)

Device Management - DeviceCommunicationControl-B (DM-DCC-B)

Alarm and Event Management - Notification - Internal-B (AE-N-I-B)

Alarm and Event Management - Information-B (AE-INFO-B)

Alarm and Event Management - Alarm Summary-A (AE-ASUM-B)

Segmentation capability No
Data link layer options

MS/TP master

Baud rates:

  • 9600
  • 19,200
  • 38,400
  • 76,800
Device address binding No static device binding supported
Networking options None
Character sets supported ISO 10646 (UTF-8)