GSAB integration setup - Johnson Controls - LIT-12014420 - RA-1270 - Airflow Measuring Station - AFMS

RA-1270 Fan Inlet Airflow and Temperature Measurement Station SA Bus Integration Application Note

Product name
AFMS
Document type
Application Note
Document number
LIT-12014420
Revision date
2024-05-17

About this task

To set up GSAB integration, use a portable PC with the CCT software tool installed and connected to the Equipment Controller, and complete the following steps:

Procedure

  1. Use the appropriate device profile in the CCT to add an SA Bus device. See Table 1.
  2. Select the points for the RA-1270 device. See Commissioning tips for more information.
  3. Set up the SA Bus device address.
    Table 1. SA Bus device profile in the CCT for the RA-1270
    SA Bus device name Description
    RA-1270 Fan inlet airflow and temperature measuring station