Selection chart - Johnson Controls - LIT-1900138 - Butterfly Valve and Actuator - Electric Actuator - M9000 Electrically Actuated, Standard-Pressure, Standard-Temperature, Two-Way Butterfly Valves (with Weather Shield)

M9000 Electric Actuator, Standard-Pressure, Standard-Temperature, Two-Way Butterfly Valves (with Weather Shield) Catalog Page

Brand
Johnson Controls
Product name
M9000 Electrically Actuated, Standard-Pressure, Standard-Temperature, Two-Way Butterfly Valves (with Weather Shield)
Document type
Catalog Page
Document number
LIT-1900138
Revision date
2019-10-02
Language
English
Table 1. M9000 Electrically Actuated, Standard-Pressure, Standard-Temperature, Two-Way Butterfly Valves (with Weather Shield)
Valve code number Size, in. Cv at 90° Cv at 70° Closeoff pressure, psig lfi1573473048134.html#lfi1573473048134__selection_chart-fn_1 Two-Way Valve with M9000 Series Electric Actuator (with Weather Shield)
Spring open Spring closed Spring open Spring closed
 

Spring return — floating control

M9220-AGA-3 without end switches

M9220-AGC-3 with 2 end switches

VWN020HB

2

144

84

175

VWN020HB+92NAGA

VWC020HB+94NAGA

VWN020HB+92NAGC

VWC020HB+94NAGC

VWN025HB

2-1/2

282

163

175

VWN025HB+92NAGA

VWC025HB+94NAGA

VWN025HB+92NAGC

VWC025HB+94NAGC

VWN030HB

3

461

267

175

VWN030HB+92NAGA

VWC030HB+94NAGA

VWN030HB+92NAGC

VWC030HB+94NAGC

VWN040LB

4

841

496

50

VWN040LB+92NAGA

VWC040LB+94NAGA

VWN040LB+92NAGC

VWC040LB+94NAGC

VWN040HB

4

841

496

175

VWN040HB292NAGA lfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC040HB294NAGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN040HB292NAGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC040HB294NAGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050LB

5

1,376

775

50

VWN050LB292NAGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC050LB294NAGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050LB292NAGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC050LB294NAGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

 

Spring return — on/off

M9220-BGA-3 without end switches

M9220-BGC-3 with 2 end switches

VWN020HB

2

144

84

175

VWN020HB+92NBGA

VWC020HB+94NBGA

VWN020HB+92NBGC

VWC020HB+94NBGC

VWN025HB

2-1/2

282

163

175

VWN025HB+92NBGA

VWC025HB+94NBGA

VWN025HB+92NBGC

VWC025HB+94NBGC

VWN030HB

3

461

267

175

VWN030HB+92NBGA

VWC030HB+94NBGA

VWN030HB+92NBGC

VWC030HB+94NBGC

VWN040LB

4

841

496

50

VWN040LB+92NBGA

VWC040LB+94NBGA

VWN040LB+92NBGC

VWC040LB+94NBGC

VWN040HB

4

841

496

175

VWN040HB292NBGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC040HB294NBGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN040HB292NBGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC040HB294NBGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050LB

5

1,376

775

50

VWN050LB292NBGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC050LB294NBGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050LB292NBGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC050LB294NBGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

 

Spring return — 0 to 10 VDC proportional control

M9220-GGA-3 without end switches

M9220-GGC-3 with 2 end switches

VWN020HB

2

144

84

175

VWN020HB+92NGGA

VWC020HB+94NGGA

VWN020HB+92NGGC

VWC020HB+94NGGC

VWN025HB

2-1/2

282

163

175

VWN025HB+92NGGA

VWC025HB+94NGGA

VWN025HB+92NGGC

VWC025HB+94NGGC

VWN030HB

3

461

267

175

VWN030HB+92NGGA

VWC030HB+94NGGA

VWN030HB+92NGGC

VWC030HB+94NGGC

VWN040LB

4

841

496

50

VWN040LB+92NGGA

VWC040LB+94NGGA

VWN040LB+92NGGC

VWC040LB+94NGGC

VWN040HB

4

841

496

175

VWN040HB292NGGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC040HB294NGGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN040HB292NGGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC040HB294NGGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050LB

5

1,376

775

50

VWN050LB292NGGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC050LB294NGGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050LB292NGGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWC050LB294NGGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

 

Two-way — non-spring return

On/off (floating) control

0 to 10 VDC proportional control

M91xx-AGA-2 without switches

M91xx-AGC-2 with 2 switches

M91xx-GGA-2 without switches

M91xx-GGC-2 with 2 switches

VWN020HB

2

144

84

175

VWN020HB+916AGA

VWN020HB+916AGC

VWN020HB+916GGA

VWN020HB+916GGC

VWN025HB

2-1/2

282

163

175

VWN025HB+916AGA

VWN025HB+916AGC

VWN025HB+916GGA

VWN025HB+916GGC

VWN030HB

3

461

267

175

VWN030HB+916AGA

VWN030HB+916AGC

VWN030HB+916GGA

VWN030HB+916GGC

VWN040HB

4

841

496

175

VWN040HB+924AGA

VWN040HB+924AGC

VWN040HB+924GGA

VWN040HB+924GGC

VWN050LB

5

1376

775

50

VWN050LB+924AGA

VWN050LB+924AGC

VWN050LB+924GGA

VWN050LB+924GGC

VWN050HB

5

1376

775

175

VWN050HB2924AGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050HB2924AGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050HB2924GGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050HB2924GGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN060LB

6

1850

1025

50

VWN060LB2924AGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN060LB2924AGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN060LB2924GGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN060LB2924GGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

 

Two-Way — non-spring return

Automatic signal detection floating, on/off, proportional

 

M93xx-HGC-2 without end switches

M93xx-HGC-2 with two end switches

VWN020HB

2

144

84

175

VWN020HB+920HGA

VWN020HB+920HGC

VWN025HB

2-1/2

282

163

175

VWN025HB+920HGA

VWN025HB+920HGC

VWN030HB

3

461

267

175

VWN030HB+920HGA

VWN030HB+920HGC

VWN040HB

4

841

496

175

VWN040HB+935HGA

VWN040HB+935HGC

VWN040LB

4

841

496

50

VWN040LB+920HGA

VWN040LB+920HGC

VWN050HB

5

1376

775

175

VWN050HB2935HGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050HB2935HGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN050LB

5

1376

775

50

VWN050LB+935HGA

VWN050LB+935HGC

VWN060HB

6

1850

1025

175

VWN060HB2935HGAlfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN060HB2935HGClfi1573473048134.html#lfi1573473048134__selection_chart-fn_2

VWN060NB

6

1850

1025

50

VWN060NB+935HGA

VWN060NB+935HGC

VWN080NB

8

3316

1862

50

VWN080NB+935HGA

VWN080NB+935HGC

1 Valves rated for 175 psig closeoff have 75 psig maximum dead-end service rating. Valves rated for 50 psig closeoff are not rated for dead-end service.
2 Valve assemblies have two actuators mounted in tandem.