  1. Go to Start > All Programs > Easylon > 852, then right-click Config 852 Interface and select Run as administrator. The Easylon IP Interface Config Settings window appears.

  2. In the window, configure the settings to match Figure 1. See Table 1 for the options to select.
    Note: The IP Configuration and Soft License Configuration sections contain information that is unique to the site configuration and the hardware installed. Do not change these settings.
    Figure 1. Easylon IP Interface Config Settings for the Loytec Configuration Server

    Table 1. Easylon IP Interface Config Settings for Use with the Loytec Configuration Server

    Field

    Selection or Entry

    Aggregation

    Must be selected with a setting of 8 ms.

    Note: This selection and its setting may be modified on a per-site basis if you wish to match the aggregation of the LCS85 with the aggregation of the Loytec router.

    Config Server Pollinterval

    Must not be selected.

    Enable Channelrouting

    May be selected if you wish to reduce traffic, but it is not required.

    Load saved channel config

    Must not be selected, otherwise the LCS85 does not communicate on the LonWorks network. Because the channel information is not saved, the configuration server must be online and communicating when the LCS85 starts up.

    Automatic Start

    Must be selected.

    as Service

    Must be selected.

  3. Click Apply.