  1. Go to Start > All Programs > Easylon > 852, then right-click Config 852 Interface and select Run as administrator. The Easylon IP Interface Config Settings window appears.

  2. In the window, configure the settings to match Figure 1. See Table 1 for the options to select.
    Note: The IP Configuration and Soft License Configuration sections contain information that is unique to the site configuration and the hardware installed. Do not change these settings.
    Figure 1. Easylon IP Interface Config Settings for the Echelon Configuration Server

    Table 1. Easylon IP Interface Config Settings for Use with the Echelon Configuration Server

    Field

    Selection or Entry

    Aggregation

    Must be selected with a setting of 8 ms.

    Config Server Pollinterval

    Must be selected with a setting of 60.

    Enable Channelrouting

    May be selected to if you wish to reduce traffic, but is not required.

    Load saved channel config

    Must be selected, otherwise the LCS85 does not communicate on the Lon network at startup if the configuration server is not running. The LCS85 must initially communicate on the Lon network before the channel configuration can be saved.

    Automatic Start

    Must be selected.

    as Service

    Must be selected.

  3. Click Apply.