Subnetwork with LN-VAVCF-12 - Johnson Controls - LIT-12011795 - LN-SVSENH-0G - LN-SVSENH-0 - LN-SVSEN-0 - LN-SVSEN-0G - Bulb controller - LN Series Communicating Sensor

LN Series Communicating Sensors Installation Instructions

Product
Network and Communications > Lonworks Networks > LN Series Communicating Sensor
Document number
LIT-12011795
Revision date
2013-01-01

When you install one or more LN-SVSENx-0 sensors with an LN-VAVCF-12 Controller, you must set the EOL terminations of only the last LN-SVSENx-0 sensor to ON. Set all EOL terminations on all other LN-SVSENx-0 sensors to OFF. The controller must be the first devices on the bus, as the EOL termination in these devices are permanently enabled (see Figure 7).