Subnetwork with LN-IOE4x-0-0 and LN-PRG6x0-12 - Johnson Controls - LIT-12011795 - LN-SVSENH-0G - LN-SVSENH-0 - LN-SVSEN-0 - LN-SVSEN-0G - Bulb controller - LN Series Communicating Sensor

LN Series Communicating Sensors Installation Instructions

Product
Network and Communications > Lonworks Networks > LN Series Communicating Sensor
Document number
LIT-12011795
Revision date
01/01/2013

When you install one or more LN-SVSENx-0 sensors with an LN-PRG6x0-12 Series Controller, set only the EOL terminations of the LN-PRG6x0-12 Series Controller and the last LN-SVSENx-0 sensor to ON. Set all other EOL terminations on the LN-SVSENx-0 sensors to OFF (see Figure 8).

When you install LN-IOE4x0-0 I/O Extension Module with an LN-PRG6x0-12 Controller and one or more LN-SVSENx-0 sensor, set only the EOL terminations on the last I/O Extension Module and the last LN-SVSENx-0 sensor to ON. Set all other EOL terminations on the I/O Extension Modules and LN-SVSENx-0 sensors to OFF (see Figure 9). LN-IOE4x0-0 I/O Extension Modules and LN-SVSENx-0 sensors EOL switches are factory-set to OFF by default.