Table 1. Parts and Construction
Part Construction

Frame

5 in. deep x 16-gauge galvanized steel

Blades

16-gauge galvanized steel, Triple V

Linkage

Concealed in the frame

Blade Pin

1/2 in. hex steel, zinc plated

Bearings

Stainless steel

Side Seal

Flexible metal compression, stainless steel

Blade Seal

Stainless steel with extruded silicone

Sleeve

20-gauge galvanized steel, 20 in. long

Side Plate

16-gauge galvanized steel

Note: The sleeve is designed for use with standard breakaway connectors. Mounting angles are provided with the damper.
Note: All leakage-rated smoke damper systems are factory-assembled, connected to a power source, and cycled a minimum of three times before shipment.