This module is implemented using a Hybrid Activity with possible states of Not Unoccupied, Unocc Htg/Clg Check, and Unoccupied Off. When the State is Not Unoccupied, the Unocc Status is set to Unocc Cntrl Not Req’d. When the State is Unoccupied Off, the State is set to Satisfied. When the State is Unocc Htg/Clg Check, the Zone Temperature inputs are monitored to determine whether unoccupied operation is required.
-
Unocc Cntrl Not Req'd: Unit does not require unoccupied sequencing.
-
Satisfied: Unoccupied sequencing is active, but zones are all satisfied.
-
Unocc Htg Clg: Unoccupied sequencing is active and zones require a mix of heating and cooling.
-
Unocc Heating: Unoccupied sequencing is active and zones require heating (only).
-
Unocc Cooling: Unoccupied sequencing is active and zones require cooling (only).
Occupancy |
Application Mode |
WarmupCooldown |
Off During Unocc |
State |
---|---|---|---|---|
NOT (Unoccupied) |
* |
* |
* |
Not Unoccupied |
Unoccupied |
Vent |
* |
* |
Not Unoccupied |
NOT (Vent) |
Warmup |
* |
Not Unoccupied |
|
Cooldown |
* |
Not Unoccupied |
||
Normal |
FALSE |
Unocc Htg/Clg Check |
||
Coast |
FALSE |
Unocc Htg/Clg Check |
||
Normal |
TRUE |
Unoccupied Off |
||
Coast |
TRUE |
Unoccupied Off |