Zone Low Limit Determination - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English

This module specifies whether a low limit condition exits. This condition is determined based on the zone temperature, the low limit setpoint, and the low limit differential. When the zone temperature drops below the low limit setpoint, the module outputs a low limit state. When the zone temperature is unreliable, the last reliable value is used in the comparison.

You can view and modify the modules in this group’s logic.