The following table describes the attributes used by the Occupied Sequencing (AHU 100% OASD) module.
Name |
Description |
Default Value |
---|---|---|
AHU-STATE (State) |
Represents the current state generated by the sequence |
Satisfied |
Cooling Control Status |
Contains the value fed back from the mechanical cooling PID controller necessary for the sequencer to determine what actions to take. |
Normal Set Name: Control Status |
Fan Ready |
Comes from the Start/Stop Sequencer and indicates that the fans and dampers have been sequenced properly. |
False |
Heat Recovery Control Status |
For proportional heat recovery devices, displays the value fed back from the heat recovery device PID necessary for the sequencer to determine what actions to take. |
Normal Set Name: Control Status |
Heat Recovery Modulated |
Used to tell the state machine if the heat recovery is modulated or not. True means modulated, and False means not modulated. |
False |
Preheat Control Status |
Contains the value fed back from the preheat PID controller necessary for the sequencer to determine what actions to take. |
Normal Set Name: Control Status |
Preheat Percent Cmd |
Position of the output controller used to prevent the preheat device from unnecessarily cycling off then back on as the air handling unit starts up. |
0.0% |
Process Variable |
Discharge air temperature. It is the variable that is compared to the setpoint to determine whether it is necessary to heat or cool the discharge air. |
13 °C, 55 °F |
Setpoint |
Contains the discharge air temperature setpoint the state generator attempts to control. |
13 °C, 55 °F |