The following table describes the attributes used by the Smoke Control Sequencing for UL-864-UUKL module.
Name |
Description |
Default Value |
---|---|---|
Emergency Mode |
Used to force the controller to respond to fire or shutdown commands. |
Normal Set Name: Emergency Modes |
Priority |
Indicates the BACnet priority for the output points. For normal control, this value is set to 16 (default). When the State is not Normal, this value is set to 2 (Automatic Fire/Life Safety Control). |
16 |
Safety Switch 1 |
Connected to a safety input (for example, high or low duct pressure or temperature). |
Normal Set Name: Normal/Alarm |
Safety Switch 2 |
Connected to a safety input (for example, high or low duct pressure or temperature). |
Normal Set Name: Normal/Alarm |
Safety Switch 3 |
Connected to a safety input (for example, high or low duct pressure or temperature). |
Normal Set Name: Normal/Alarm |
Safety Switch 4 |
Connected to a safety input (for example, high or low duct pressure or temperature). |
Normal Set Name: Normal/Alarm |
Shutdown Delay |
Amount of time in seconds to remain in the Pre-Shutdown state prior to transitioning to Shutdown. This attribute also specifies the delay from Shutdown to Normal after the Mode and/or Safety Switches are cleared. |
180 Seconds |
SMOKE SEQUENCE-STATE (State) |
Indicates the current mode of the state generator. |
Set Name: Emergency States See Primary States (Smoke Control Sequencing for UL-864-UUKL). |