Smoke Control Sequencing for UL-864-UUKL - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English

The Smoke Control Sequencing for UL-864-UUKL module processes the emergency command and determines the current emergency mode. This module accepts the emergency command, four safety switch inputs, and a shutdown delay duration. The module has state and priority outputs. The priority output provides UL 864 UUKL smoke control support where you can write to the hardware points at a high priority during an emergency.

For information on how the FSM determines the state, see FSM (Emergency Mode).

Note: For a UL approved project, you must use the currently approved software version.