Status AND - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English

The Status AND module examines up to 9 Enum inputs and outputs a unified Enum status for the input group, a Boolean output indicating whether any status equals OFF, and a Boolean output indicating whether all statuses equal ON. The module accepts nine ON/OFF inputs and a cascaded input for cases where you need more than eight inputs, and has outputs for any input OFF, all inputs ON, and status.

This module is implemented as a Control Activity.

You can view and modify the modules in this group’s logic.

Figure 1. Status AND Logic