About this task

Before you perform a step test, consider the possible mechanical system damage or occupant comfort issues that may occur by overriding the output.

Procedure

  1. Set trends for the output and controlled variable. Set intervals for 10 seconds for the duration of the test.
  2. Override the output to close the device completely, and allow the controlled variable to settle.
  3. Override the output to open the device completely, and allow the controlled variable to settle.