Close (Heating): Damper Percent Cmd is set to 0% (maximum heating).
-
Open (Cooling): Damper Percent Cmd is set to 100% (maximum heating).
-
Hold Damper: Damper Percent Cmd is held at its last value.
-
Control: Damper Percent Cmd is modulated based on the PID output to control the Process Variable to the Effective Setpoint.
Mode |
ZN-T Reliable |
Shutdown Option |
Unreliable Option |
PID Tuning Reset |
State |
---|---|---|---|---|---|
Shutdown |
* |
Open (Cooling) |
* |
* |
Open (Cooling) |
* |
Close (Heating) |
* |
Close (Heating) |
||
* |
Hold Damper |
* |
Hold Damper |
||
Hold |
* |
* |
* |
Reset 1st PID |
Control |
Hold |
TRUE |
* |
* |
* |
Hold Damper |
Not (Shutdown) |
TRUE |
* |
* |
Control |
|
FALSE |
Open (Cooling) |
Open (Cooling) |
|||
Close (Heating) |
Close (Heating) |
||||
Hold Damper |
Hold Damper |