Primary States (Lighting) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English
  • Lights On: The Present Value is on in this state. If the input switches to off, the state changes to Lights Blink if Warn Occupant is True. Otherwise, the state changes to Lights Off.

  • Lights Off: The Present Value is off in this state. If the input switches to on, the state changes to Lights On.

  • Lights Blink: The Present Value is off in this state. If the input remains off for 2 seconds, the state changes to Waiting to Turn Off. If the input remains off and Warn Occupant changes to False, the state changes to Lights Off. If the input switches to on, the state changes to Lights On.

  • Waiting to Turn Off: The Present Value is on in this state. If the input remains off for a period of time longer than the Light Shutoff Delay, the state changes to Lights Off. If the input remains off and Warn Occupant changes to False, the state changes to Lights Off. If the input switches to on, the state changes to Lights On.