The following table describes the attributes used by the Heating 2 Position Valve modules:
Name |
Type
1
|
Description |
Default Value |
---|---|---|---|
Control Band |
V |
Control band for the MSC. |
Display Units: °C, °F |
Control Status |
V |
Current saturation status of the controller. |
Overridden Set Name: Control Status |
Eff Minimum Off Time |
V |
Contains the minimum off time used by the MSC. |
Display Units: Seconds |
Eff Minimum On Time |
V |
Contains the minimum on time used by the MSC. |
Display Units: Seconds |
Eff Process Time Const |
V |
Contains the effective process time constant used by the MSC. |
Display Units: Seconds |
Eff Process Variable |
V |
Contains the Process Variable used by the MSC. |
Display Units: °C, °F |
Failsoft Value |
Contains the value of the output when commanded to Failsoft. |
0.0% |
|
HeatingCooling |
Configures the module to be either compatible with a heating source or a cooling source. |
Heating Set Name: Heating/Cooling |
|
HTG-ABSEFFORT (Heating Absolute EWMA Effort) |
Provides an EWMA based on the absolute value of (Current Present Value - Last Present Value). The PID computes this value. |
0.0 Display Units: % |
|
HTG-ABSERROR (Heating Absolute EWMA Error) |
Provides an EWMA based on the absolute value of (Setpoint - Process Variable). The PID computes this value. |
0.0 Display Units: °C, °F |
|
HTG-ERROR (Heating EWMA Error) |
Provides an EWMA based on the difference of (Setpoint - Process Variable). The PID computes this value. |
0.0 Display Units: °C, °F |
|
HTG-EWMA (Heating EWMA Present Value) |
Provides an EWMA of the Present Value. The PID computes this value. |
0.0 Display Units: % |
|
HTG-MINOFF or SUPHTG-MINOFF (Minimum Off Time) |
Contains the Min Off Duration for all stages. |
120 Seconds |
|
HTG-MINON or SUPHTG-MINON (Minimum On Time) |
Contains the Min On Duration for all stages. |
120 Seconds |
|
HTG-O or SUPHTG-O (Percent Cmd) |
V |
Controls the single actuator that is providing heating. |
Display Units: % |
HTG-OUTSTATE or SUPHTG-OUTSTATE (State) |
G, V |
Current operational state of the output controller. |
Set Name: COM Valve Out |
Limited Max Value |
Specifies that when commanded to Limited Max, this is the value for the Percent Cmd. |
100,0% |
|
Mode |
Mode requested by State Selection. |
Off Set Name: COM Valve Out |
|
Output Overridden |
Indicates when the actual output controlled by this output is overridden by a user. |
False |
|
Output Position |
Provides the current Present Value of the output that this controller drives. |
0% |
|
PID Tuning Reset |
Causes the PID objects to reset their tuning parameters to the default based on the appropriate Process ID. |
Normal Set Name: PID Tuning Reset |
|
PMAC Period |
V |
Contains the period used by the PMAC algorithm portion of the MSC. |
Display Units: Seconds |
Process Units |
Specifies the units for the PID. For this particular module, °C and °F are the only two valid values. |
°C, °FSet Name: Unit |
|
Process Variable |
Specifies that when the mode is set to Control, this is the variable that is controlled. Typically connected to the Zone Temperature. |
22 °C, 72 °F |
|
Setpoint |
Desired setpoint for the process variable to be controlled to when the mode is set to Control. |
22 °C, 72 °F |
C - Configuration Mode Only, G - Default Element (Generated State, if applicable), SC - Simulation and Commissioning Modes Only, V - Calculated Value (Outputs)