All inputs use their last reliable value while unreliable.
-
If the outdoor air temperature is unreliable while in the Low OA Temperature mode, the module switches to the Limited Max mode as shown in the Command Hierarchy table.
-
If the Low Limit Process Variable is unreliable while in the Remain In Control mode, the module switches to the Failsoft mode as shown in the Command Hierarchy table.