Off: Turn everything off. The Percent Cmd is set to 0%.
-
Max: Open the valve. The Percent Cmd is set to 100%.
-
Limited Max Heating: The valve is opened to the Limited Max Heating Value. This state may be used for unoccupied heating.
-
Limited Max Cooling: The valve is opened to the Limited Max Cooling. This state may be used for unoccupied heating.
-
Hold: Hold the outputs at their current position.
-
Water Flush: The valve is opened to the Water Flush Position.
-
Heating T Control: Adjust the valve output to control the Process Variable. If the Process Variable is reliable, the module controls the output in order to maintain the Process Variable at the Heating Setpoint. The Valve Percent Cmd and the Percent Cmd are adjusted between 0% and 100%.
-
Cooling T Control: Adjust the valve output to control the Process Variable. If the Process Variable is reliable, the module controls the output in order to maintain the Process Variable at the Cooling Setpoint. The Valve Percent Cmd and the Percent Cmd are adjusted between 0% and 100%.
-
Failsoft Heating: The valve is opened to the Failsoft Heating Value. This state may be used when the control temperature is unreliable.
-
Failsoft Cooling: The valve is opened to the Failsoft Cooling Value. This state may be used when the control temperature is unreliable.
-
Low OA Temperature: The valve is opened to the Low OA Temperature Position when the OA Temperature is less than the Low OA Temperature Setpoint.
-
Remain In Control: Modulate the valve to control the Limit Variable to the Limit Setpoint. If the Limit Variable is reliable, the module controls the output in order to maintain the Limit Variable at the Limit Setpoint. This mode should only be used as a shutdown strategy to add energy to the duct when the fan is off. It should not be used for general temperature control.
Summer Winter |
Cooling Mode |
Heating Mode |
Low Limit Process Variable is Reliable |
OA Temperature is Reliable |
PID Tuning Reset |
State |
---|---|---|---|---|---|---|
* |
Hold |
* |
* |
* |
Reset 1st PID |
Cooling T Control |
Hold |
* |
* |
* |
Reset 2nd PID |
Heating T Control |
|
* |
Hold |
* |
* |
Reset 1st PID |
Heating T Control |
|
* |
Hold |
* |
* |
Reset 2nd PID |
Cooling T Control |
|
Winter |
* |
Off |
* |
* |
* |
Off |
Hold |
* |
* |
* |
Hold |
||
Water Flush |
* |
* |
* |
Water Flush |
||
Max |
* |
* |
* |
Max |
||
Limited Max |
* |
* |
* |
Limited Max Heating |
||
T Control |
* |
* |
* |
Heating T Control |
||
Failsoft |
* |
* |
* |
Failsoft Heating |
||
Low OA Temperature |
* |
TRUE |
* |
Low OA Temperature |
||
* |
FALSE |
* |
Limited Max Heating |
|||
Remain In Control |
TRUE |
* |
* |
Remain In Control |
||
FALSE |
* |
Failsoft Heating |
||||
Summer |
Off |
* |
* |
* |
* |
Off |
Hold |
* |
* |
* |
* |
Hold |
|
Water Flush |
* |
* |
* |
* |
Water Flush |
|
Max |
* |
* |
* |
* |
Max |
|
Limited Max |
* |
* |
* |
* |
Limited Max Cooling |
|
T Control |
* |
* |
* |
* |
Cooling T Control |
|
Failsoft |
* |
* |
* |
* |
Failsoft Cooling |
|
Low OA Temperature |
* |
* |
TRUE |
* |
Low OA Temperature |
|
* |
FALSE |
* |
Limited Max Cooling |