No Flow: This mode closes the OAD and de-energizes the minimum injection fan.
-
Max Flow: This mode opens the OAD and energizes the minimum injection fan.
-
Start: This mode opens the OAD and the minimum injection fan is turned off. This mode sequences the damper and the fan to ensure the damper is opening before the fan is energized.
-
Min Flow Control: The minimum OA Damper is opened, and the flow is controlled by the PID block. The PID block increases the injection fan speed as the flow drops below the flow setpoint. This module does not have flow setpoint reset based on CO2 or some other indoor air quality parameter, but another module could be connected to the flow setpoint input which does reset the flow setpoint.
-
Hold: Holds the outputs at their current position. If the Output Overridden is true, then the Output Position input is passed to the Cooling Percent Cmd.
Mode |
Minimum OA Flow Reliable |
Unrel Flow Mode |
Min Flow Control Enable |
Damper Ready |
PID Tuning Reset |
State |
---|---|---|---|---|---|---|
* |
* |
* |
* |
False |
* |
Start |
* |
* |
* |
* |
True |
* |
Max Flow |
* |
* |
* |
* |
* |
* |
|
Hold |
Reset 1st PID |
Min Flow Control |
||||
Hold |
* |
* |
* |
* |
* |
Hold |
No Flow |
* |
* |
* |
* |
* |
No Flow |
Max Flow |
* |
* |
TRUE |
TRUE |
* |
Max Flow |
FALSE |
* |
Start |
||||
FALSE |
* |
* |
No Flow |
|||
Emergency Flow |
* |
* |
* |
TRUE |
* |
Max Flow |
FALSE |
* |
Start |
||||
Min Flow Control |
TRUE |
* |
TRUE |
TRUE |
* |
Min Flow Control |
FALSE |
* |
Start |
||||
FALSE |
* |
* |
No Flow |
|||
FALSE |
No Flow |
* |
* |
* |
No Flow |
|
Flow |
TRUE |
TRUE |
* |
Max Flow |