Attributes (N2 VMA DD Mode Input) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English

The following table describes the attributes used by this module.

Table 1. N2 VMA DD Mode Input Attributes
Name Type 1 Description Default Value
Cooldown Command   When true, this input places the VAV Box Controller into a cooldown mode of operation. False
System Mode   Indicates the system mode necessary to achieve the state desired based on the inputs.
  • 0: Cool Only
  • 1: Heat Only
  • 2: Fan Only
  • 3: Water Flush
  • 4: Purge
  • 5: Auto
Cool Only
Unit Enable   Indicates the method to use to close the box when Shutdown Closed is required.
  • 0: Shutdown
  • 1: Enable
Shutdown
VAV Box Mode Input   Indicates the VAV Box Mode Command used by the N2 based VMA14xx Series Controllers.
  • 0: Shutdown Closed
  • 1: Shutdown Open
  • 2: Warmup
  • 3: Water System Flush
  • 4: Low Limit
  • 5: Satisfied
  • 6: Cooling
  • 7: Heating
Shutdown Closed
Warmup Command   When true, this input places the VAV Box Controller into a warmup mode of operation. False
Warmup Cooldown   Indicates that a Warmup or Cooldown mode is required.
  • 0: Normal
  • 1: Warmup
  • 2: Cooldown
  • 3: Coast
Normal
Water Flush   When true, this input forces the VAV Box Controller into a Water Flush mode of operation. False
1 C - Configuration Mode Only, G - Default Element (Generated State, if applicable), SC - Simulation and Commissioning Modes Only, V - Calculated Value (Outputs)