Attributes (N2 Occupancy Mode Output - ASC) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English

The following table describes the attributes used by the module.

Table 1. N2 Occupancy Mode Output ASC Attributes
Name Type 1 Description Default Value
Occupancy Mode  

The effective occupancy of the controller.

  • 0=Occupied
  • 1=Unoccupied
  • 2=Bypass
  • 3=Standby
Occupied
Occupied Status V The Occupancy mode indicated by the AHU, UNT, VAV Controller.
  • True=Occupied
  • False=Unoccupied
False
Temp Occ Status V The temporary occupancy status indicated by the AHU, UNT, VAV Controllers.
  • True=Temporary Occupied
  • False=Normal
False
1 C - Configuration Mode Only, G - Default Element (Generated State, if applicable), SC - Simulation and Commissioning Modes Only, V - Calculated Value (Outputs)