N2 Compatibility Network Outputs - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English

The following table lists the network outputs associated with the N2 compatibility options.

Table 1. Network Outputs

Output

Description

Application

Compatibility

VAVSD

VAVDD

Heat Pumps

Fan Coil

Unit Vent

Rooftop

AHU

VMA 1400

VAV 100

AHU/ NT

NOCOOL

Inadequate Cooling - Indicates that the VAV box has reached maximum cooling capacity and that the zone temperature is too warm.

X

X          

X

X

 

NOHEAT

Inadequate Heating - Indicates that the VAV box has reached maximum heating capacity and that the zone temperature is too cool.

X

X          

X

X

 

STARVBOX

Starved Box - Indicates that the VAV box is open to maximum position and that the airflow is below the flow setpoint.

X

           

X

X

 
STARVEBOX Starved Exhaust Box - Indicates that the VAV box exhaust damper is open to maximum position and that the airflow cannot reach the differential flow setpoint.

X

X          

X

X

 

ACACT

Autocal Active - Indicates that the VAV box is performing an auto-calibration sequence.

X

X          

X

X

 

WC-S

Warmup Status - Indicates that the VAV box is in warmup mode.

X

             

X

 
OCC-S

Occupied Status - Indicates that the VAV box is in occupied mode.

X

X            

X

 
STBY-S

Standby Status - Indicates that the VAV box is in standby mode.

X

             

X

 

STARVCD

Starved Cold Duct - Indicates that the cold duct damper is at 100% and cannot achieve the cold duct flow setpoint.

  X           X X  

STARVHD

Starved Hot Duct - Indicates that the hot duct damper is at 100% and cannot achieve the hot duct flow setpoint.

  X           X X