The following table lists the network inputs associated with the N2 compatibility options.
Input |
Description |
Type |
Application |
Compatibility |
||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
VAVSD |
VAVDD |
Heat Pumps |
Fan Coil |
Unit Vent. |
Rooftop |
AHU |
VMA 1400 |
VAV 100 |
AHU/ UNT |
|||
Heating Available |
Indicates to the controller whether box heating and supplemental heating are available. |
Boolean |
X |
X |
||||||||
Water Flush Input |
Indicates the controller should be in a water flush mode. In this mode, the heating water valves are driven open to the flush position (default is 100%). |
Boolean |
X |
X | X | X | X |
X |
X |
X |
X |
|
VAV Box Mode Input |
Indicates the VAV Box Mode that the controller should be in. |
Enum |
X |
X |
X |
|||||||
N2 Common Setpoint |
Indicates the common setpoint for a controller. |
Float |
X |
X | X | X | X | X |
X |
|||
OA Fraction |
Indicates the percentage of outside air that is in the supply air stream. |
Float |
X |
X |
||||||||
Occupancy Schedule |
Indicates VMA14xx occupancy schedule enumeration. |
Enum |
X |
X |
X |
|||||||
Autocal Request |
Commands the controller to perform an auto-calibration. |
Boolean |
X |
X |
X |
|||||||
Setpoint Threshold |
Indicates the setpoint threshold that causes the controller to take an immediate action when the user changes the setpoint. |
Float |
X |
X |
X |
|||||||
OCCOVRTM |
Occ Ovrd Time - Indicates the amount of time that the controller remains in Temporary Occupancy mode. |
Float |
X |
X | X | X | X | X |
X |
X |
||
OCCTIME | Occ Ovrd Time - Indicates the amount of time that the controller remains in Temporary Occupancy mode. | Float | X | X | X | X | ||||||
FANSP% |
Speed Setting - Indicates the Series Proportional fan operating speed. |
Float |
X |
X |
X |
|||||||
OCC-C |
Occupied Command - Indicates whether the operation is occupied or unoccupied. |
Boolean |
X |
X | X | X | X | X |
X |
X |
X |
|
STBY-C |
Standby Command - Indicates standby mode. Active if occupied command is false. |
Boolean |
X |
X | X | X | X | X |
X |
|||
FANONSP |
Fan On Threshold - Indicates the point at which the Parallel or Series fan turns on. |
Float |
X |
X |
||||||||
FANOFFSP |
Fan Off Threshold - Indicates the point at which the Parallel or Series fan turns off. |
Float |
X |
X |
||||||||
FANONSP |
Reheat Fan On Threshold - Indicates the point at which the Parallel or Series fan turns on. |
Float |
X |
X |
||||||||
FANOFFSP |
Reheat Fan Off Threshold - Indicates the point at which the Parallel or Series fan turns off. |
Float |
X |
X |
||||||||
WUP-C |
Warmup Command - Indicates whether the unit is using warmup mode. |
Boolean |
X |
X | X | X | X | X |
X |
X |
X |
|
BOXCLSE |
Shutdown Box Close Cmd - Commands the VAV box to drive fully closed. |
Boolean |
X |
X |
X |
|||||||
SDWN-C |
Shutdown Box Open Cmd - Commands the VAV box to drive fully open. |
Boolean |
X |
X |
||||||||
SPRAMPST |
Ramp Rate - Indicates the speed at which the VAV Supply Fan ramps up on startup. |
Float |
X |
X |
||||||||
VENT-C |
Vent Command - Commands the unit into ventilation mode. |
Boolean |
X | X | X |
X |
X |
|||||
PRGE-C |
Purge Command - Commands the unit into purge mode. |
Boolean |
X | X |
X |
X |
||||||
SDWN-C |
Shutdown Command - Commands the AHU unit to turn off. |
Boolean |
X | X | X | X |
X |
X |
||||
COOLDOWN |
Cooldown Command - Indicates whether the unit is using cooldown mode. |
Boolean | X | X | ||||||||
MSTRFLOW-S |
Master Flow Setpoint HFR Status - Indicates status of the Master VAV box and commands the subordinate VAV box to match the status. |
Enum | X | X |