Fans (OASD) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 16.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
16.0
Revision date
2023-10-02
Language
English

These selections provide the logic for the main fans.

The selection options for Fans are:

Supply Fan

  • Single Speed

  • Variable Speed

    • Two Duct Static Pressure Sensors

  • Dual Supply Fans

    • Run Together

    • Lead/Lag

    • Run/Standby

  • Fan Status

    • Fan Array
      • Analog Fan Status

    • Number of Fans

      • Three

      • Four

      • Five

      • Six

      • Eight

      • Nine

      • Ten

      • Twelve

      • Fifteen

      • Sixteen

    • Loss of Airflow Strategy

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

  • Alarm Management

    • Lockout Switch

    • Frequency Converter Fault

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

    • Motor Overload Tripped

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

    • Belt Alarm

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

  • Separate Damper Command for Fan
    • Damper Status

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

Exhaust Fan

  • Single Speed

  • Variable Speed

    • Volume Matching

      • Velocity Pressure (Pitot Tube)

      • Flow Measurement (Scaled)

      • Separate Occupied and Unoccupied Flow Setpoints

    • Building Static Pressure

    • Track Supply Fan

  • Dual Exhaust Fans

    • Run Together

    • Lead/Lag

    • Run/Standby

  • Fan Status

    • Fan Array
      • Analog Fan Status

    • Number of Fans

      • Three

      • Four

      • Five

      • Six

      • Eight

      • Nine

      • Ten

      • Twelve

      • Fifteen

      • Sixteen

    • Loss of Airflow Strategy

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

  • Alarm Management

    • Lockout Switch

    • Frequency Converter Fault

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

    • Motor Overload Tripped

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

    • Belt Alarm

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

  • Separate Damper Command for Fan
    • Damper Status

      • Automatic Restart

      • Manual Restart

        • Unit Reset Switch (BI)

Supplemental Exhaust Fan

  • Toilet Exhaust Fan

    • Fan Status

      • Loss of Status Strategy

        • Automatic Restart

        • Manual Restart

          • Unit Reset Switch (BI)

    • Alarm Management

      • Lockout Switch

      • Motor Overload Tripped

        • Automatic Restart

        • Manual Restart

          • Unit Reset Switch (BI)

    • Blocking Protection

  • General Exhaust Fan

    • Fan Status

      • Loss of Status Strategy

        • Automatic Restart

        • Manual Restart

          • Unit Reset Switch (BI)

    • Alarm Management

      • Lockout Switch

      • Motor Overload Tripped

        • Automatic Restart

        • Manual Restart

          • Unit Reset Switch (BI)

    • Blocking Protection

A Supply Fan is required (that is, it is selected by default) as well as an optional Exhaust or Relief Fan.

A Variable Speed Supply Fan is required in order to select a Variable Speed Exhaust Fan.