These selections provide the logic for the main fans.
The selection options for Fans are:
Supply Fan
-
Single Speed
-
Variable Speed
-
Fan Status
-
Loss of Airflow Strategy
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
-
Alarm Management
-
Lockout Switch
-
Frequency Converter Fault
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
Motor Overload Tripped
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
Belt Alarm
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
- Separate Damper Command for Fan
-
Damper Status
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
Exhaust Fan
-
Single Speed
-
Variable Speed
-
Volume Matching
-
Velocity Pressure (Pitot Tube)
-
Flow Measurement (Scaled)
-
Calculate Discharge Flow from Cold and Hot Deck Flow Inputs
-
Separate Occupied and Unoccupied Flow Setpoints
-
-
Building Static Pressure
-
Track Supply Fan
-
-
Fan Status
-
Loss of Airflow Strategy
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
-
Alarm Management
-
Lockout Switch
-
Frequency Converter Fault
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
Motor Overload Tripped
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
Belt Alarm
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
- Separate Damper Command for Fan
-
Damper Status
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
Supplemental Exhaust Fan
-
Toilet Exhaust Fan
-
Fan Status
-
Loss of Status Strategy
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
-
Alarm Management
-
Lockout Switch
-
Motor Overload Tripped
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
-
Blocking Protection
-
-
General Exhaust Fan
-
Fan Status
-
Loss of Status Strategy
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
-
Alarm Management
-
Lockout Switch
-
Motor Overload Tripped
-
Automatic Restart
-
Manual Restart
-
Unit Reset Switch (BI)
-
-
-
-
Blocking Protection
-
A Supply Fan is required (that is, it is selected by default) as well as an optional Exhaust or Relief Fan.
A Variable Speed Supply Fan is required in order to select a Variable Speed Exhaust Fan.