The following table describes the attributes used by the Occupied Sequencing (AHU 100% OADD) module.
Name |
Description |
Default Value |
---|---|---|
CD-STATE (State) |
Represents the current state generated by the sequence. |
Satisfied |
Cooling Control Status |
Contains the value fed back from the mechanical cooling PID controller necessary for the sequencer to determine what actions to take. |
Normal Set Name: Control Status |
Fan Ready |
Comes from the Start/Stop Sequencer and indicates whether the fans and dampers have been sequenced properly. |
False |
Heat Recovery Control Status |
For proportional heat recovery devices, specifies the value fed back from the heat recovery device PID necessary for the sequencer to determine what actions to take. |
Normal Set Name: Control Status |
Heat Recovery Modulated |
Contains a configuration input used to tell the state machine if the heat recovery is modulated or not. True means modulated and False means not modulated. |
False |
Preheat Control Status |
Contains the value fed back from the preheat PID controller necessary for the sequencer to determine what actions to take. |
Normal Set Name: Control Status |
Preheat Percent Cmd |
Position of the output controller. This attribute is used to prevent the preheat device from unnecessarily cycling off then back on as the air handling unit starts up. |
0.0% |
Process Variable |
Contains the cold deck discharge air temperature. It is the variable that is compared to the setpoint and is used to determine whether it is necessary to heat or cool the discharge air. |
13 °C, 55 °F |
Setpoint |
Contains the cold deck temperature setpoint the state generator attempts to control. |
13 °C, 55 °F |