Damper Minimum Position Reset by CO2 - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18
Language
English

This module is designed to reset the damper minimum position based on the space CO2. The module has an input for the space CO2, two inputs to define the CO2 reset band (CO2 Reset A and CO2 Reset B), and two inputs for damper minimum position and the low and high ends of the band (Min Pos Low Setpoint and Min Pos High). This module has an output for the Damper Minimum Position.

You can view and modify the modules in this group’s logic.