Primary States (WarmupCooldown Determination) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18
Language
English
  • Normal: No warmup/cooldown is required based on the Network Input. Warmup is activated only if the supply air temperature is greater than the zone temperature by more than the differential.

  • Warmup: The heating and cooling temperature setpoints adjust to the occupied values and go to the heating states to control to the heating setpoint.

  • Cooldown: The heating and cooling temperature setpoints adjust to the occupied values and turn all heating modes off (does not affect this module.)

  • Coast: The heating and cooling temperature setpoints adjust to the unoccupied values (does not affect this module).