Staged Box Heating Control v50 - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18
Language
English
Important: As of Release 5.0, the Staged Box Heating Control v50 module replaces the Staged Box Heating Control module.

The Staged Box Heating Control Module is designed to control staged devices within a VAV single duct control application. This module also incorporates tracking the overridden value of the actual output object (AO, PAO). The module resets the PIDs to default tuning parameters if the Reset PID Tuning input is not Normal.

You can view and modify the modules in this group’s logic.