Attributes (N2 Occupancy Mode Input) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 15.0

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
15.0
Revision date
2022-11-18
Language
English

The following table describes the attributes used by this module.

Table 1. N2 Occupancy Mode Input Attributes
Name Type 1 Description Default Value
Occupancy Schedule  

The Occupancy Schedule using the enum set for N2 based controllers.

  • 0=Unoccupied
  • 1=Stand By
  • 2=Occupied
  • 3=No Schedule
Unoccupied
Input SC The amount of time in minutes that temporary occupancy is active. 60.0 minutes
Occ Schedule   The Occupancy Schedule using the standard application enum set.
  • 0=Occupied
  • 1=Unoccupied
  • 2=Standby
  • 3=Not Set
Occupied
Output V The amount of time in seconds that temporary occupancy is active. 0 seconds
1 C - Configuration Mode Only, G - Default Element (Generated State, if applicable), SC - Simulation and Commissioning Modes Only, V - Calculated Value (Outputs)