The state output is generated from the Network mode and Hardware mode inputs based on the Resolution Mode setting. The following table shows the command hierarchy used to determine whether the State should be Normal or Energy Hold Off.

Table 1. Energy Hold Off Determination Command Hierarchy

Resolution Mode

Network Reliable

Network Mode

Hardware Reliable

Hardware Mode

State

Network Priority

True

Normal

*

*

Normal

Energy Hold Off

*

*

Energy Hold Off

False

*

True

Normal

Normal

Energy Hold Off

Energy Hold Off

False

*

Normal

Hardware Priority

*

*

True

Normal

Normal

Energy Hold Off

Energy Hold Off

True

Normal

False

*

Normal

Energy Hold Off

False

*

Energy Hold Off

False

*

False

*

Normal

Either Can Activate

True

Normal

False

*

Normal

True

Normal

Normal

Energy Hold Off

Energy Hold Off

Energy Hold Off

*

*

Energy Hold Off

False

*

True

Normal

Normal

Energy Hold Off

Energy Hold Off

False

*

Normal