Resetting Tuning Parameters at CCT/PCT Release 5.0 and Earlier (No Network Input or Tuning Reset Connection) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 13.1

Controller Tool Help

Brand
Johnson Controls
Metasys
Product name
Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
13.1
Revision date
2019-12-04
Language
English

About this task

You can reset the tuning parameters by opening the logic of the module that contains the active PID and doing one of the following:
  • Change the PID's Reset Tuning input from False to True, click Apply, change the input back to False, and click Apply.
  • Change the PID Pre-Processor's Process ID to something other than what you are using, click Apply, change it back to what you are using, and click Apply.