If the low limit process variable is unreliable, the damper closes and the fan de-energizes unless commanded to Emergency Open.

If the flow sensor is unreliable, module commands the fan off and the damper closed or it commands the fan on and the damper open based on a user selection.

All other inputs use their last reliable value while unreliable.