Reliability (Min OA Damper Proportional Output) - Johnson Controls - Metasys - LIT-12011147 - Software Application - Controller Configuration Tool - 13.1

Controller Tool Help

Product
Controls > Control Tools > Controller Configuration Tool
Document type
User Guide
Document number
LIT-12011147
Version
13.1
Revision date
2019-12-04

If the low limit process variable is unreliable, the damper closes unless commanded to Emergency Open. All other inputs use their last reliable value while unreliable.