The following table describes the attributes used by the Min OA Damper 2 Position modules.
Name |
Type 1 |
Description |
Default Value |
---|---|---|---|
Damper OpenClose |
V |
Contains the control signal for the Damper output. The enumeration set only has two values, Close and Open. |
Close Set Name: Close/Open |
DAMPER-OUTSTATE or MOAD-OUTSTATE (State) |
V, G |
Represents the current module mode of operation. |
Close Set Name: Close/Open/Hold |
Low Limit Delay |
Defines the time the damper remains closed once the low limit process variable rises above the low limit setpoint minus the Low Limit Proportional Band. |
180 Seconds |
|
Low Limit Process Variable |
Contains the low limit temperature process variable. This temperature is usually the mixed air temperature or the preheat air temperature. |
7 °C, 45 °F |
|
Low Limit Proportional Band |
Specifies the amount below the Low Limit Setpoint that the Low Limit Process Variable is allowed to fall before the damper closes. |
0 °C, 0 °F |
|
Low Limit Setpoint |
Upper threshold for the low limit process function. |
7 °C, 45 °F |
|
Mode |
Desired mode of operation. |
Close Set Name: AHU Two Pos Damper |