Pressurize: This mode opens the OAD and closes the RAD and EAD.
-
Depressurize: This mode opens the EAD and closes the RAD and OAD.
-
Close: This mode opens the RAD and closes the EAD and OAD.
-
Purge: This mode opens the EAD and OAD and closes the RAD.
-
Min OA: This mode puts the EAD and OAD to minimum position. The RAD is 100% - Min Pos.
-
Hold: This mode holds the dampers in their last position.
-
Ramp Min OA: This mode ramps the EAD and OAD to Min Pos at a controlled ramp rate. The RAD position is the complement of the EAD position.
-
Ramp Open: This mode ramps the EAD and OAD open at a controlled ramp rate. The RAD position is the complement of the EAD position.
-
T Control: This is the free cooling mode. The OAD is modulated to allow outdoor air for cooling purposes. The EAD position is the same as the OAD position, and the RAD position is the complement of the OAD position. The OAD and EAD modulate between the minimum position and 100%.
FSCS OAD Cmd 1 |
FSCS EAD Cmd1 |
FSCS RAD Cmd 11 |
PID Tuning Reset |
Mode |
State |
---|---|---|---|---|---|
!Auto |
* |
* |
* |
Pressurize |
Pressurize |
Auto |
!Auto |
* |
* |
Depressurize |
Depressurize |
Auto |
Auto |
!Auto |
* |
Close |
Close |
Auto |
Auto |
Auto |
* |
Purge |
Purge |
Auto |
Auto |
Auto |
* |
Min OA |
Min OA |
Auto |
Auto |
Auto |
Reset 1st PID |
Hold |
T Control |
Auto |
Auto |
Auto |
* |
Hold |
Hold |
Auto |
Auto |
Auto |
* |
Ramp Min OA |
Ramp Min OA |
Auto |
Auto |
Auto |
* |
Ramp Open |
Ramp Open |
Auto |
Auto |
Auto |
* |
T Control |
T Control |