The following table lists the network outputs associated with the N2 compatibility options.
Output |
Description |
Application |
Compatibility |
||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
VAVSD |
VAVDD |
Heat Pumps |
Fan Coil |
Unit Vent |
Rooftop |
AHU |
VMA 1400 |
VAV 100 |
AHU/ NT |
||
NOCOOL |
Inadequate Cooling - Indicates that the VAV box has reached maximum cooling capacity and that the zone temperature is too warm. |
X |
X |
X |
X |
||||||
NOHEAT |
Inadequate Heating - Indicates that the VAV box has reached maximum heating capacity and that the zone temperature is too cool. |
X |
X |
X |
X |
||||||
STARVBOX |
Starved Box - Indicates that the VAV box is open to maximum position and that the airflow is below the flow setpoint. |
X |
X |
X |
|||||||
STARVEBOX | Starved Exhaust Box - Indicates that the VAV box exhaust damper is open to maximum position and that the airflow cannot reach the differential flow setpoint. |
X |
X |
X |
X |
||||||
ACACT |
Autocal Active - Indicates that the VAV box is performing an auto-calibration sequence. |
X |
X |
X |
X |
||||||
WC-S |
Warmup Status - Indicates that the VAV box is in warmup mode. |
X |
X |
||||||||
OCC-S |
Occupied Status - Indicates that the VAV box is in occupied mode. |
X |
X |
X |
|||||||
STBY-S |
Standby Status - Indicates that the VAV box is in standby mode. |
X |
X |
||||||||
STARVCD |
Starved Cold Duct - Indicates that the cold duct damper is at 100% and cannot achieve the cold duct flow setpoint. |
X | X | X | |||||||
STARVHD |
Starved Hot Duct - Indicates that the hot duct damper is at 100% and cannot achieve the hot duct flow setpoint. |
X | X | X |