Table 1. Notification class
Property name Required Optional Proprietary Property ID Data type Writable Range
OBJECT_IDENTIFIER     75 BACnet Object Identifier    
OBJECT_NAME     77 CharacterString    
OBJECT_TYPE     79 BACnet ObjectType    
ACK_REQUIRED     1 BACnet Event Transition Bits  
PRIORITY     86 BACnet ARRAY[3] of Unsigned  
RECIPIENT_LIST     102 BACnet LIST of BACnet Destination  
DESCRIPTION     28 CharacterString 40 characters max
NOTIFICATION_CLASS     17 Unsigned    
ITEM_REFERENCE     32527 CharacterString    
USER_NAME     2390 CharacterString 400 characters max
STATUS     512 Enumerated    
ENABLED     673 Boolean  
EXECUTION_PRIORITY     2197 Enumerated 0–3
OBJECT_CATEGORY     908 Enumerated 0–111
ALARM_STATE     1006 Enumerated    
ROUTE_TO_METASYS     32580 Boolean